Navigation:Refrigeration/cooling/refrigeration equipment engineering-Shanghai Ying Xiang refrigeration equipment limited >> News >>

Frequently asked questions refrigeration equipment, you know?

Release time:2016-11-03 17:04:07
Refrigeration system equipment and refrigerant piping installation and overall design of cold storage and freezer for daily use, must be in strict accordance with the specifications, any design, installation is not regulating the use, maintenance or irregular situations, are going to make bad refrigeration system, or even result in machine failure and damage.
 
1, refrigeration compressor unit not installed vibration or vibration reduction effect
According to the standard installation, the whole unit should be installed damper, ifirregular or there is no damping of vibration reduction measures, would make the machine vibration powerful, easily lead to line bouncing, vibration equipment, even the vibration of the engine room.
 
2, refrigerant piping or lack oil return bends
Conveying refrigeration agent of pipeline in by horizontal steering Shang bent Shi, must made a first to sagging Hou to up of small bent that u type bent, such pipeline again to uplink only qualified, cannot directly made 90 degrees steering uplink, or, system inside of oil on cannot is good of returned to compressor in to, and large deposition in cold machine in, makes wind machine and whole system cannot normal play role, even damaged wind machine and unit equipment.
 
3 unbalanced, refrigerant piping connection
Unit piping connected to a set of more than one compressor, oil return to equilibrium of the compressor, main interface must be set in the middle of the head position,and then set the branch pipe to the side, let the oil balance into multiple branch pipe of the compressor.
 
Moreover, the branch pipe to install valves in order to adjust back to oil. If this is notthe case, but drawn from different parts of on the main followed by multiple downpipes connected to more than one compressor, will return imbalance, the first oil isalways the most, followed by an order for return oil decreases. This way, it may appear in the first compressor malfunction vibrating huge, high oil pressure, overheatingof unit, which led to the compressor red cylinders hold such accidents, damage to the equipment.
 
4, pipe without insulation
If there is no insulation, Frost formation on cold pipes at ambient temperature, thusaffecting the performance, to increase the load and make the unit run super, reducethe service life.
 
5, to periodically check the technical indicators, adjust
System operating temperatures and pressures of high and low, of lubricants and refrigerants, to check and adjust. Systems should have an automatic control and compressor alarm device, whenever there is a problem, it will issue a warning, or automated protective shutdown, shutdown of the compressor.
 
6, unit maintenance
To regularly change the oil and filter. Add refrigerant as necessary. Condenser to keep clean, keep clean to avoid dust, sand or flying debris, effect of cooling effect.
 
The view was expressed that lubricants as long as there is no impurities, can continue to be used, although it has been used for more than two years, without replacement. This is clearly wrong. Lubricant system running at high temperatures for a long time, its performance may have been changed, cannot play its proper lubrication, if not replace, will make the machine run temperatures, or even engine damage.
 
Filters should be replaced on a regular basis. We know that the machines have a "filter", also have to be replaced periodically. Refrigeration compressor system may not"filter", there is only one filter, should be replaced periodically. If the filters are made of metal, not damage does not have to change this view is unfounded and untenable.
 
7, air-conditioning installation and maintenance issues
Inside the air cooler cold storage location and environment, will affect its functioning. Near the near the refrigerator door cooler, prone to condensation of frost. Location due to its environment is in the door, hot air outside the door to enter, in the face of wind machines, condensing frosting, or icing. Although air coolers can be scheduled to automatically defrost heating, however, if you open the door too frequently,takes too long to open, heat flow into the long and big enough Fan defrost effect on the poor. Because the cooler defrost time cannot be too long, otherwise the cooling time is relatively short, bad refrigeration effect, Cuvin cannot be guaranteed.
 
Cold storage, due to too many doors, open the door too frequently, too long, nothing measures, there are partition walls, inside and outside the direct exchange of cold and hot air, cooler near the door is bound to suffer a serious Frost problems.
 
8, air coolers defrost when melt water drainage problem
The problem associated with the severe degree of frost. Because the wind machine frosting seriously, inevitably producing large quantities of condensate water fan water tray to bear, poor drainage, simply fall down, flow to the ground within a library, if there are store goods, it will soak the goods. In this case, you can install drain pan,and install a thick draft tube, excluding condensate water.
 
Cooling fan blew water from the fan, is sprayed on the problems of inventory in thewarehouse. It is also hot and cold wind machine frosting problem in the Exchange environment, mainly fan fan page under thermal environment produced by condensation of water, instead of the Fan defrost effect problems. To resolve fan condensingwater problem, the environment must be improved. Design of partition walls in thegarage door, you cannot cancel the partition walls. In order to facilitate access to the goods, and partition walls, fan the environment has changed, just not up to the cooling effect, defrosting the effect is bad, even the fan failure-prone, equipment problems.
 
9, the condenser fan motor and air electrical heater problem
This is a wearing part. Long-running fan motor in a high temperature environment, failures and damages may occur. If the cold storage to ensure the temperature is important, you want to order some fragile parts, so that timely repairs, air coolers electric heating tube, but also need to have spares to be safe.
 
10, the cold temperature and the refrigerator door problems
A cold storage room, how large, how much inventory, how many doors open, doorsopening and closing time and frequency, inventory turnover frequency, cargo throughput, are factors that affect temperature in the library.
 
Cold warehouse door opened and closed in one day the number should not be more than 8 times. If an infinite number of switches, mechanical components refrigeratory automatic doors and a border insulation material will accelerate wear and electrical components are also more prone to failure. If the cold storage area, automatic doors less, number each automatic door switch, machinery is overburdened, there will be failure-prone, door accessories are also frequent damage. In this way, maintenance workload increases, and the timeliness of maintenance problems. Because manufacturers cannot arrange a person to wait for this one (maybe cold only two doors).However, once the refrigerator door has failed, not be open in time, will affect the incoming and outgoing goods; or does not shut down, it will make the cold temperatures, the temperature does not meet requirements. Wikipedia article source refrigeration.
 
Construction of cold storage design, and the number set and refrigerator door, must be based on the amount of stock, the switching frequency, integrated arrangement. Cold storage units are also based on the design specifications, the rational use ofcold storage cannot be regardless of the actual conditions of design condition and facilities, increase inventory and improve the freight turnover, more than normal load and capacity of the facility and equipment. Otherwise, there will be a lot of problems.
 
11, cold storage fire safety
Generally about knocked cold storage, due to the low temperature and is not suitable for installation of fire sprinkler systems. Therefore, cold storage fire need to paymore attention. Despite the low temperature cold storage conditions, but if a fire occurs, there is combustible material in the library, especially stocks tend to have packed cartons and, it is easy to burn. Therefore, the fire risk is also great for cold storage, cold storage must be no Fireworks.
 
Meanwhile, cooler and wire, power cords, electric heating, also always check, eliminating electrical fire hazards.
 
12, the ambient temperature of the condenser problems
Condenser is usually installed in the outdoor work on the roof, in the environment of high temperature in the summer, the temperature of the condenser itself is very high, the unit operating pressure. If the hot weather, can build on the roof condensation gazebo, Sun, the condenser temperature is reduced in order to reduce pressuremachine, protection equipment, so as to ensure the purpose of cold temperature. Of course, if enough can ensure the temperature, can also build patio.