Navigation:Refrigeration/cooling/refrigeration equipment engineering-Shanghai Ying Xiang refrigeration equipment limited >> News >>

How to judge the refrigeration equipment is working properly?

Release time:2016-11-07 15:04:55
Summary
How refrigeration systems for valves and equipment, compressor suction and discharge valve, oil separator-import and export valves, condensers, refrigeration equipment such as import and export of the accumulator valve is working properly?
1, the condensing pressure and condensation temperature, the surface pressure corresponding to the evaporation temperature, evaporation depends on temperature and pressure according to the refrigeration temperature, evaporation pressure and compressor suction pressure should be in the running. Condensing temperature andpressure depends on the temperature and flow of cooling medium. Under normal circumstances, for a standard series of refrigeration compressors, condensing pressure not exceeding 1.8MPa of R22 and R717 (gauge pressure). Operation, the condensing pressure and compressor discharge pressure, liquid receiver pressure similar to, if not similar is not normal.
 
2, closed shell and tube condenser cooling water pressure above 0.12MPa, and must guarantee the inlet water temperature and amount of water and air cooled condensers should maintain a certain degree of air temperature, air flow and surface wind speed in the wind. Touch the closed shell and tube condenser shell, upper heat lowershould be cool. Vertical condenser water inlet temperature is about 2~4℃ range, about leaves, horizontal condenser.
 
3, the refrigerant in the liquid level to meet the requirements. Typical reservoir fluidlevel should be at 1/3~2/3 location of liquid level indicator.
 
4, the use of automatic automatic oil return pipe for oil separator with oil return, seasonable heat in cold weather, hot and cold cycles for about 1h. Cooling system liquid line filter, solenoid valve coil running should be warm, the temperature difference between the before and after there should be clear, Frost and condensation can appear, or is blocked.
 
5, frost or condensation of the throttle valve body uniform, thick frosting are not allowed entrance. When the liquid refrigerant through the throttle valve and hear onlydull small sound.
 
6 the protection equipment, refrigeration equipment, such as safety valves, bypass valves opening and close flexibly, control devices, pressure controllers, pressure controllers, temperature controllers setting value should be correct and normal. Pressuregauge needle should be stable, flexible pointer. Thermometer indicating correct.