Navigation:Refrigeration/cooling/refrigeration equipment engineering-Shanghai Ying Xiang refrigeration equipment limited >> News >>

Refrigeration equipment cleaning and maintenance tips

Release time:2016-11-30 16:14:07
Refrigeration refrigeration equipment can be divided into different compression refrigeration and absorption refrigeration system in two ways. As refrigeration equipment, refrigerating efficiency will gradually decrease, and careful analysis is made up of the following causes, following along with the bacteria to get to know it!
 
Scale of a circulating water system causes
 
A variety of salts dissolved in natural waters, such as bicarbonate, sulfate, chloride, silicates, etc. Therefore, if you use bicarbonate containing more water as cooling water, when it through the heat exchanger at the heat transfer surface, when heated to decomposition. Equivalent of an aeration process of cooling water through the cooling tower, escape of CO2 dissolved in the water, so water has a PH value will rise. At this point, the bicarbonate will react under alkaline conditions.
 
Therefore, in the heat exchanger of heat transfer on the surface, these micro-solubility salt is very easy to reach saturation point, and crystallizes out of the water. Whenthe flow rate when comparing or comparison of heat transfer surfaces rough, thesecrystals sediment deposition on heat transfer surface. In addition, the water dissolves the calcium sulfate, calcium silicate, magnesium silicate, when the anion and cation concentrations when the product exceeds its solubility, sediment deposited on the heat transfer surface is also generated. These sediments are usually referred to asscale. Because the scale is composed of inorganic salts, so it is also referred to as inorganic scale due to crystallization of these scales compact, hard, so called hard scale. They are usually firmly attached to the heat on the surface, not easy to rinse.
 
Hazards:
 
1, lower heat 3%--10%;
 
2, easy to block the condenser pipe, ranging from reduced traffic, effect of cooling effect. Steel tubes for condenser in serious and even blocked, as well as scrap;
 
3, to provide a forum for some anaerobic bacteria.
 
Second, corrosion of metals in water circulating system causes
 
Chemical cleaning for cooling water system in normal operation as well as sound, fen is often different forms of corrosion.
 
According to the theory of knowledge of metal corrosion, through careful observation of corrosion test specimens of metal corrosion or damage to your equipment form, in conjunction with a number of other ways, people can find out the cause of thecorrosion and measures to solve the problem, so the study of metal corrosion in cooling water system of forms is a very useful method.
 
1 uniform corrosion
 
Uniform corrosion and pitting corrosion and general corrosion. Its general characteristics are short-range metal corrosion on all exposed surfaces evenly. In the corrosion process, gradually thin metal, and finally destroyed.
 
Outline of carbon, uniform corrosion occurs mainly in low-PH acidic solution. If youadd too much acid, cooling water at low PH reduced to carbon steel corrosion of the equipment will also be significant.
 
2 galvanic corrosion
 
Also known as bi-metal corrosion or galvanic corrosion contact corrosion.
 
When two different metals are invaded at the time of conductivity of aqueous solutions, often there is a potential difference between the two metals. One example of galvanic corrosion in cooling water system is the brass heat exchanger tubes and carbon steel plate or steel between the water in the cooling water of galvanic corrosion. In the corrosion process, accelerated corrosion is a very thick steel pipe or waterChambers, rather than a thin copper tube. Due to steel pipe plate or Chamber wall is thicker, so can long-term use.
 
3 crevice corrosion
 
Immersion in corrosion of metal surfaces, or when it is at a gap when other hidden areas, often strong local corrosion.
 
Third, the cleaning process
 
Cleaning of heat exchangers, the traditional process often uses mineral acids such as hydrochloric acid or sulfuric acid cleaning, inorganic acid cleaning descaling is not only poor, and high corrosion rate, serious corrosion to equipment, resulting in riskof leakage of heat exchangers. For high values of heat-exchange equipment, greaterrisk of traditional process of cleaning equipment obsolete.